0C2280
CIRCUIT BREAKERS, SUBSTATION
1200 Amp, SIEMENS, TYPE SP-72.5-40-1,72.5 KV, 1988, 125 VDC CLOSE & TRIP
Ref:
42391
CB-18909
ONE (1) 1200 AMP SIEMENS SF6 CIRCUIT BREAKER
TYPE SP-72.5-40-1
1.0 K RATE VOLTAGE RANGE FACTOR
3 CYCLE INTERRUPT
40 KA SHORT CYCLE
60 HERTZ
10 KA RATED OUT OF PHASE CURRENT
350 KV BIL
80 PSIG FILL PRESSURE
75 PSIG OPERATING PRESSURE
65 PSIG MINIMUM OPERATING PRESSURE
70 PSIG ALARM PRESSURE
65 PSIG CUT-OUT PRESSURE
3705 LBS WITH GAS
PNEUMATIC MECHANISM
125 VDC CLOSE & TRIP
115 VAC HTR. & COMP. VOLTAGE
RATED CAPACITANCE CURRENT SWITCHING
2.0 OVERVOLTAGE FACTOR
100 AMP LINE CHARGING
630 AMP ISOLATED BANK SWITCH
630 AMP BACK-TO-BACK SWITCH
25 KA INRUSH PEAK
3360 HZ INRUSH FREQUENCY
6X600:5 MRCT'S, C200
INSTRUCTION BOOK PB-3468-03
SHORT LINE FAULT EXPOSURE REQUIRES 5000 PF CAPACITOR ON LINE
WITHIN 30' OF BREAKER
Belyea Co Inc
2200 Northwood Ave
Easton PA 18045-2239
Tel:
610-515-8775
Fax:
610-258-1230
Email (Request Quote):
info@belyeapower.com
Web:
www.belyeapower.com
|