0T5306
TRANSFORMERS, 3 PHASE, 60 CYCLE, SUBSTATION
5000/5600 KVA, Pri 26400 D, Sec 4160Y/2400, GENERAL ELECTRIC:1
Ref:
40069
T-5721
ONE (1) 5000/5600 KVA GENERAL ELECTRIC SUBSTATION TRANSFORMER, 3 PHASE,
60 HERTZ, CLASS OA/FFA, 55/65 DEG. C RISE, 6.1% IMPEDANCE, DRAIN
AND SAMPLE VALVE, PRESSURE RELIEF VALVE, LIQUID TEMPERATURE GAUGE,
LIQUID LEVEL GAUGE, VACUUM PRESSURE GAUGE, PRESSURE RELIEF DEVICE,
TOP X TOP MOUNTED BUSHINGS, NON-REMOVABLE RADIATORS, FANS CAN BE
ADDED TO GET UNIT TO 6250/7000 KVA RATING, S/N F965952A
HIGH VOLTAGE: 26400 DELTA BIL: 200 KV
LOW VOLTAGE: 4160Y/2400 BIL: 75 KV
TAPS: 27100-26400-25700-25000-24300
TOTAL WEIGHT: 26,900 LBS.
CORE & COILS: 12,500 LBS.
TANK & FIT.: 7,700 LBS.
OIL: 6,700 LBS. (900 GALS.)
Dimensions:
148"H
116"H COV
12" LV BU
32" HV BU
96" Deep over Rad
80" Long or Wide
Belyea Co Inc
2200 Northwood Ave
Easton PA 18045-2239
Tel:
610-515-8775
Fax:
610-258-1230
Email (Request Quote):
info@belyeapower.com
Web:
www.belyeapower.com
|