0B4010
BOILERS, WATERTUBE
75000 PPH, Babcock & Wilcox, 750 PSI/750 F Superheat, Low NOx, Gas/#2 oil, 2.5 ppm Ultra-Low NOx Option, various ages
Ref:
670671
|
|
|
Nationwide Boilers low NOx 75,000 pph, 750 psig / 750°F design, superheat steam, trailer-
ounted package
watertube boiler is set to burn natural gas or #2 oil. It is fully piped and wired and includes the
ollowing components:
Low NOx Burner
EconoStak Economizer
Burner Management System
Parallel Positioning Combustion Controls
Forced Draft Fan, Motor & Starter
Complete Fuel Train & Pilot Ignition System
#2 Fuel Oil Pump
Water Column & Site Glass
Steam Pressure Gauge
Low-water Cutoffs
Safety Valves
Feedwater Stop & Check Valves
Blowdown Valves
Continuous Blowdown Metering Valve
Chemical Feed Valve
Single Element Feedwater Regulator with Pre-piped
3-Valve Bypass
Steam Non-return Valve (loose)
Stack (loose)
NEMA 4 Electrical Enclosures
Low NOx CataStak SCR System (optional)
Weatherproofed (except for freezing)
Meets FM, NFPA 85 & IRI Insurance Standards
Operating Manuals
Fuel Consumption:
Natural Gas:99,000 SCFH @ 15-25 psi reg.
#2 Oil:745 GPH
Connection Sizes:
Main Steam:8"-600# FLG
Natural Gas: 4"-150# FLG
#2 Oil Supply / Return:2" NPT / 1" NPT
Feedwater:2½"-600# FLG
Bottom Blowdown:1½"-600# FLG
Continuous Blowdown:¾" NPT
Chemical Feed:½" NPT
Atomizing Air / Steam: 2" NPT / 3"-150# FLG
Instrument Air:½" NPT
Water Column Drain:¾" NPT
Electrical Power Service Requirements:480 VAC, 3 ph, 60 hz, 200 amp
Boiler Dimensions & Weights:
Length / Width / Height:61' 4" / 10' 0" / 14' 0"
Shipping Weight:126,000 lbs
Operating Weight:170,000 lbs
Emissions Data (natural gas):
NOx (corr. to 3:30 ppm